MONITORING SMS FUNCTIONALITY
|
SMS functionality is available for systems with
our SM32/36 supervisory module.
Using an additional GSM modem connected to
the SM32/36 supervisory module by a RS232
cable, up to 15x priority based mobile phone
numbers can receive system alarm status
reports via SMS.
When prompted individual SMS system status
reports can also be sent to your mobile phone.
This status report contains; the site name, the
actual bus voltage, the actual rectifier current,
the actual load current of the battery time
remaning. It will also include the first of any
major alarm if present.
Configuration/setup of mobile phone numbers
and parameters can be made through our
SM32/36 configuration software. GSM data
logging of SMS activity can be read and
saved through this software also.
- Alarm and system status reports sent via SMS.
- Simple setup and configuration.
- Data logging of SMS activity.
|
 |
| Specifications |
View Brochure |
|
|
| Hardware Requirements |
|
| Supervisory & Monitoring Module: |
SM32/SM36 supervisory module. |
| Modem: |
Wavecom fastrack series GSM modem. |
| Connection: |
Serial: 1x RS232 cable for connection between supervisory module and modem. |
|
|
| Software Requirements: |
Version 17 or above. |
| SMS Length And Formatting |
|
| SMS Message Type: |
Unicode. |
| Characters Per SMS: |
x70 maximum. |
| SMS Strings: |
1. Status strings (ST), the x2 status strings (ST1, ST2) consist of up to x4 variable name-value pairs.
- Bus voltage (in volt), value has x4 characters maximum. (xxx or xx.x)
- Rectifier current (in amps), value has x4 characters maximum. (xxxx)
- Load current (in amps), value has x4 characters maximum. (xxxx)
- Calculated battery time remaining (in hrs/mins, only sent if value is less than 1 day),
value has x5 characters maximum. (hh:mm)
2. Alarm name (AN), Up to x20 characters.
3. Site name (SN), Up to x11 characters.
4. Ack by string (AB), Up to x20 characters. |
| Types Of SMS Sent: |
1. Unsolicited alarm messages (Alarm SMS)
2. Acknowledge messages (Ack by SMS)
3. Status Messages (Status SMS)
|
|
|
| Generated Alarm SMS |
|
| Major Alarm List: |
1. Rectifier mains fail.
2. Urgent rectifier fail.
3. Bus low voltage.
4. Bus low float.
5. Bus high voltage.
6. LVD1 operate on.
7. Load current high.
|
|
|
| Part Number |
|
| ASM-GSMKIT: |
SMS functionality kit, including the required software, 1x Wavecom fastrack series GSM modem
and 1x RS232 cable for connection. |