- Universal input range.
- Hot-swap replacement in shelf.
- Back feed protection.
- Redundant fan design.
- Redundant power supply design.
- Fast transfer time, typically less than ¼ cycle.
- Wide operation temperature range -20 to +70°C.
- Lower audible noise <55dBA.
- Emergency power off function embedded.
- No-cross connect.
- Optional maintenance bypass
switch function with interlock.
- Operation priority setup of transfer
side by setting in controller module. |
Specifications |
|
|
|
| Input |
|
| AC Voltage Range: |
110/115/120V AC: From 89 to 138V AC. |
|
208/220/240V AC: 176 to 276V AC. |
| Over Voltage Threshold: |
|
| Adjustable Using Controller: |
220 to 240V AC for 208V AC systems.
233 to 252V AC for 220V AC systems.
244 to 264V AC for 230V AC systems.
254 to 276V AC for 240V AC systems.
117 to127V AC for 110V AC systems.
122 to 132V AC for 115V AC systems.
127 to 138V AC for 120V AC systems. |
| Under Voltage Threshold: |
|
| Adjustable Using Controller: |
176 to 198V AC for 208V AC systems.
176 to 209V AC for 220V AC systems.
185 to 218V AC for 230V AC systems.
193 to 228V AC for 240V AC systems.
89 to 105V AC for 110V AC systems.
93 to 110V AC for 115V AC systems.
100 to 114V AC for 120V AC systems. |
| Redundant Power Supply Design: |
Startup power-on by priority source or alternative. |
|
|
| Output |
|
| Waveform: |
Sinusoidal. |
| Nominal Output Voltage: |
Same as mains AC or the output of inverter modules. |
| Permissible Frequency Area: |
Max. ±2.5% (Synchronize area of inverter).
±1.5Hz for 60Hz inverter.
±1.25Hz for 50Hz inverter. |
| Transfer Time: |
Typical ¼ cycle. |
| Rated Current: |
50A (All voltage settings). |
| Operation Methods: |
Inverter priority or utility priority (Programmable). |
|
|
| Part Number |
|
| SBM12000: |
50A/12kVA static bypass module. |