| Specifications |
View Brochure | Modular Rectifiers | Monitoring |
|
|
|
AC Input
|
|
|
Voltage Range:
|
312-500V AC (full power output)
156-312V AC (reduced output power)
|
|
Frequency Range:
|
45-66Hz
|
|
Power Factor:
|
>0.99 (full load)
|
|
Style:
|
3-phase neutral and earth.
|
| Surge Protection: |
MOV; 3x Ph-N, 1x N-Earth. (spark gap)
In(8/20µS): 20kA
Imax(8/20µS): 40kA |
|
|
|
|
DC Output
|
|
|
Nominal Voltage:
|
-48V
|
|
Float Voltage Range:
|
43-60V
|
|
Maximum Power Output:
|
54000W
|
|
Polarity:
|
Positive earth.
|
|
DC Distribution:
|
56x positions for 18mm wide DIN rail mount circuit breakers.
May be arranged in many configurations of loads and batteries. Fuse options also available. (options)
|
|
LVD Options:
|
Single battery LVD fitted as standard.
Up to 2x LVDs with independent control may be fitted on battery or load side. (option)
|
|
LVD Rating:
|
600A
|
|
Supervisory & Monitoring Module:
|
SM31 (standard)
SM32 TCP/IP enabled for web based viewing & configuration. (option)
|
| Supervisory Module Mounting: |
Door mounted for improved system terminal access. |
|
Alarms:
|
1x fixed alarm – “Monitor failed” Up to 9x user configurable, 2 of which are pre-programmed: Non-urgent summary alarm, Urgent summary alarm, 7x unassigned, may be assigned to any one of 37 alarm events, (e.g. rectifier fail, mains fail etc.) on an “AND” or “OR” basis. Contacts rated for 1A at 60V DC
|
|
|
|
|
Environmental
|
|
|
Ambient Temperature:
|
-10˚C to +70˚C (maximum power de-rated above +50˚C)
|
|
Humidity:
|
5-95% (non-condensing)
|
|
Altitude:
|
<2500m, De-rate maximum ambient temperature by +4˚ per 1000m above sea level.
|
|
|
|
|
Mechanical
|
|
|
Dimensions W, H, D:
|
600mm (23.6”), 19” standard mounting rails, 600mm (23.6”), 2000mm (78 ¾”) 40U of rack space.
|
|
Weight:
|
180kg (approx)
|
|
|
| Part Numbers: |
Actual part numbers will vary with congifuration.
Contact us for further details on a solution that suits your requirements. |