| Specifications |
View Brochure | Modular Rectifiers | Monitoring |
|
|
|
AC Input
|
|
|
Voltage Range:
|
312-500V AC (full power output)
156-312V AC (reduced output power)
|
|
Frequency Range:
|
45-66Hz
|
|
Power Factor:
|
>0.99 (full load)
|
|
Style:
|
3-phase neutral and earth.
|
| Surge Protection: |
MOV; 3x Ph-N, 1x N-Earth. (spark gap)
In(8/20µS): 20kA
Imax(8/20µS): 40kA |
|
|
|
|
DC Output
|
|
|
Nominal Voltage:
|
-48V
|
|
Float Voltage Range:
|
43-60V
|
|
Maximum Power Output:
|
27000W
|
|
Polarity:
|
Positive earth.
|
|
DC Distribution:
|
16x load positions for 18mm wide circuit breakers, plus 4x battery breakers up to 125A each.
May be arranged in different configurations of load and battery breakers. Fuse options also available. (options)
|
|
LVD Options:
|
Single battery LVD fitted as standard.
Up to 2x LVDs with independent control may be fitted on battery or load side. (option)
|
|
LVD Rating:
|
600A
|
| Supervisory Module Mounting: |
Door mounted for improved system terminal access. |
|
Supervisory & Monitoring Module:
|
SM31 (standard)
SM32 TCP/IP enabled for web based viewing & configuration. (option)
|
| Battery Condition Monitoring: |
Optional full battery monobloc monitoring. (bloc voltage & string current) |
|
Alarms:
|
1x fixed alarm – “Monitor failed” Up to 9x user configurable, 2 of which are pre-programmed: Non-urgent summary alarm, Urgent summary alarm, 7x unassigned, may be assigned to any one of 37 alarm events, (e.g. rectifier fail, mains fail etc.) on an “AND” or “OR” basis. Contacts rated for 1A at 60V DC
|
|
|
|
|
Environmental
|
|
|
Ambient Temperature:
|
-10˚C to +70˚C (maximum power de-rated above +50˚C)
|
|
Humidity:
|
5-95% (non-condensing)
|
|
Altitude:
|
<2500m, De-rate maximum ambient temperature by +4˚ per 1000m above sea level.
|
|
|
|
|
Mechanical
|
|
|
Dimensions W, H, D:
|
600mm (23 ½”) , 19” standard mounting rails 450mm (17 ¾”), 800mm (31 ½”) providing 15U of rack space.
|
|
Weight:
|
75kg (approx)
|
|
|
|
|
Compliances
|
|
|
Safety:
|
EN60950
|
|
|
| Part Numbers: |
Actual part numbers will vary with congifuration.
Contact us for further details on a solution that suits your requirements. |