| Specifications |
View Brochure | Modular Rectifiers | Monitoring |
|
|
|
AC Input
|
|
|
Voltage Range:
|
312-500V AC (full power output)
156-312V AC (reduced output power)
|
|
Frequency Range:
|
45-66Hz
|
|
Power Factor:
|
>0.99 (full load)
|
|
Style:
|
3-phase neutral and earth.
|
| Surge Protection: |
MOV; 3x Ph-N, 1x N-Earth. (spark gap)
In(8/20µS): 20kA
Imax(8/20µS): 40kA |
|
|
|
|
DC Output
|
|
|
Nominal Voltage:
|
-48V
|
|
Float Voltage Range:
|
43-60V
|
|
Maximum Power Output:
|
27000W
|
|
Polarity:
|
Positive earth.
|
|
Load Distribution:
|
Priority: 6x 18mm MCBs.
Non-Priority: 5x 18mm MCBs, 2x 100A DIN00 fuses, 2x 160A DIN00 fuses.
|
| Battery Distribution: |
2x 400A DIN02 fuses. |
|
LVD Options:
|
2x LVDs with independent control on load side.
|
|
LVD Rating:
|
Priority: 400A
Non-Priority: 200A
|
|
Supervisory & Monitoring Module:
|
SM31 (standard)
SM32 TCP/IP enabled for web based viewing & configuration. (option)
|
|
Alarms:
|
1x fixed alarm – “Monitor failed” Up to 9x user configurable, 2 of which are pre-programmed: Non-urgent summary alarm, Urgent summary alarm, 7x unassigned, may be assigned to any one of 37 alarm events, (e.g. rectifier fail, mains fail etc.) on an “AND” or “OR” basis. Contacts rated for 1A at 60V DC
|
|
|
|
|
Environmental
|
|
|
Ambient Temperature:
|
-10˚C to +70˚C (maximum power de-rated above +50˚C)
|
|
Humidity:
|
5-95% (non-condensing)
|
|
Altitude:
|
<2500m, De-rate maximum ambient temperature by +4˚ per 1000m above sea level.
|
|
|
|
|
Mechanical
|
|
|
Dimensions W, H, D:
|
600mm (23.6”), 600mm (23.6”), 1600mm (63”), providing 33U of rack space.
|
|
Weight:
|
120kg (approx)
|
|
|
| Part Numbers: |
Actual part numbers will vary with congifuration.
Contact us for further details on a solution that suits your requirements. |