AC Input
|
|
|
Voltage Range:
|
312-500V AC (full power output)
156-312V AC (reduced output power)
|
|
Frequency Range:
|
45-66Hz
|
|
Power Factor:
|
>0.99 (full load)
|
|
Style:
|
3-phase neutral and earth.
|
| Surge Protection: |
MOV; 3x Ph-N, 1x N-Earth. (spark gap)
In(8/20µS): 20kA
Imax(8/20µS): 40kA |
|
|
|
|
DC Output
|
|
|
Nominal Voltage:
|
-48V
|
|
Maximum Power Output:
|
16000W
|
|
Polarity:
|
Positive earth.
|
|
Load & Battery Distribution:
|
24x load positions for 18mm wide circuit breakers, plus 3x battery breakers up to 100A each.
May be arranged in different configurations of load and battery breakers. (option)
|
|
LVD Options:
|
Single battery LVD fitted as standard.
Up to 2x LVDs with independent control may be fitted on load side. (option)
|
|
LVD Rating:
|
400A
|
|
Supervisory & Monitoring Module:
|
SM31 (standard)
SM32 TCP/IP enabled for web based viewing & configuration. (option)
|
| Supervisory Module Mounting: |
Door mounted for improved system terminal access. |
|
|
|
|
Environmental
|
|
|
Ambient Temperature:
|
-10˚C to +70˚C (maximum power de-rated above +50˚C)
|
|
Humidity:
|
5-95% (non-condensing)
|
|
Altitude:
|
<2500m, De-rate maximum ambient temperature by +4˚ per 1000m above sea level.
|
|
|
|
|
Mechanical
|
|
|
Dimensions W, H, D:
|
600mm (23.6”), 600mm (23.6”), 2200mm (86.6”)
|
|
Weight:
|
1000kg when fitted with 4 strings of 180Ahr batteries. (approx)
|
|
|
|
|
Compliances
|
|
|
Safety:
|
EN60950
|
|
|
| Part Numbers: |
Actual part numbers will vary with congifuration.
Contact us for further details on a solution that suits your requirements. |