| Specifications |
View Brochure | Modular Rectifiers | Monitoring |
|
|
| AC Input |
|
| Voltage Range: |
312-500V AC (full power output) 156-312V AC (reduced output power) |
| Maximum Input Current: |
120A/ph (ph-N) |
| Frequency Range: |
45-66Hz |
| Power Factor: |
>0.99 (full power) |
| Style: |
3-phase neutral and earth. |
| Surge Protection: |
MOV; 3x Ph-N, 1x N-Earth.
In(8/20µS): 20kA
Imax(8/20µS): 40kA |
|
|
| DC Output |
|
| Nominal System Output Voltage: |
-48V |
| Maximum Power Output: |
From 54000W scalable to over 300kW. |
| Polarity: |
Positive earth. (standard) |
| Load & Battery Distribution: |
56x positions for 18mm wide DIN rail mount circuit breakers.
May be arranged in many configurations of loads and batteries. Fuse options also available. (options) |
| Low Voltage Disconnect Options: |
Single battery LVD fitted as standard.
Up to 2x LVDs with independent control may be fitted on battery or load side. (option) |
| LVD Current Rating: |
1200A |
| Supervisory & Monitoring Module: |
SM31 (standard) SM32 TCP/IP enabled for web based viewing & configuration. (option) |
| Supervisory Module Mounting: |
Door mounted for improved system terminal access. |
| Battery Condition Monitoring: |
Optional full battery monobloc monitoring. (bloc voltage & string current) |
|
|
| Environmental Requirements |
|
| Temperature: |
-10°C to +70°C (max. power de-rated above 50°C) |
| Humidity: |
5-95% RH (non-condensing) |
| Altitude: |
<2500m, De-rate maximum ambient temperature by 4°C per 1000m above sea level. |
|
|
| Mechanical |
|
| Dimensions W, D, H: |
600mm (23.6”), 19” standard mounting rails, 600mm (23.6”), 2000mm (78 ¾”) 40U of rack space. |
| Weight: |
180kg (approx) |
|
|
| Compliances |
|
| Safety: |
EN60950 |
|
|
| Part Numbers: |
Actual part numbers will vary with congifuration.
Contact us for further details on a solution that suits your requirements. |