| Specifications |
View Brochure |
|
|
|
AC Input
|
|
|
Nominal:
|
110/220V, 50/60Hz
|
|
Voltage Range:
|
100-275V AC (full power output), 85-100V AC (reduced power output)
|
|
Frequency Range:
|
45-66Hz
|
|
Power Factor:
|
>0.99 (full load)
|
|
Efficiency:
|
88%
|
|
Input Fuses:
|
HRC Fuses in phase & neutral.
|
|
Maximum Input Current:
|
8.5A
|
|
Protection:
|
Input Voltage: Automatic shutdown, restarts automatically when correct voltage restored.
Input Rush: <2x maximum input current.
|
|
|
|
DC Output
|
|
|
Nominal Voltage:
|
48V
|
|
Rated Voltage:
|
58V
|
|
Voltage Range:
|
45-60V
|
|
Maximum Current:
|
12A
|
|
Regulation:
|
Line: ±0.1% Load: ±0.5% (no load to full load)
|
|
Hold-up Time:
|
>15ms for 20% output voltage drop.
|
|
Start-up Time:
|
Walk-in delay 2 seconds (depends on AC input voltage)
|
|
Protection:
|
Current Limit: Adjustable to 50-100% of maximum rated current.
Over Temp: Automatic current turndown, backup shutdown protection.
Polarity Reversal: Output fuse with crowbar diode.
Over Voltage: Adjustable limit
|
|
Noise:
|
Ripple <100Hz: <5mV rms unweighted
Voice Band 100Hz to 5KHz: <0.5mV rms psophometric
Wide Band 5kHz to 1 MHz: <2.5mV rms unweighted
Peak to Peak 0 to 20MHz: <50mV p-p unweighted
|
|
Isolation:
|
Input to Output: 3000V AC
Input to Chassis: 2500V AC (VDR to chassis removed.)
Output to Chassis: 1500V AC
|
|
|
|
Environmental
|
|
|
Ambient Temperature:
|
25+/-5°C
|
|
Range:
|
-10 to +60°C
|
|
Humidity:
|
5-95% RH (non-condensing)
|
|
Altitude:
|
<2500m, De-rate maximum ambient temperature by +4˚ per 1000m above sea level.
|
|
|
|
Mechanical
|
|
|
Dimensions, W, H, D:
|
311mm, 163mm, 62mm
|
|
Weight:
|
1.5kg
|
|
|
| Compliances: |
Electrical Safety: EN 60950,
RF Emissions: CISPR 22 Class B,
RF Immunity: CISPR 24,
AC Harmonics: EN 61000-3-2,
AC Flicker and Fluctuation: EN 610003-3,
RoHS: 2002/95/EC,
Consumer Safety: CE |