| Specifications |
View Brochure | Modular Rectifiers | Monitoring |
|
|
|
AC Input:
|
Three phase or single phase. (refer to RM series brochures for full details)
|
|
Frequency Range:
|
45-66Hz |
|
Power Factor:
|
>0.99 (full load) |
|
Termination:
|
Three phase, 6mm² L1, L2, L3, N, E tunnel terminals.
(Single phase by linking L1, L2, L3 terminals) |
|
|
|
DC Output
|
|
|
Nominal Voltage:
|
-48V |
|
Rated System Output Power:
|
6000W |
|
Polarity:
|
Positive earth. (negative earth available to special order) |
|
DC Distribution:
|
Load: 2x 10A, 2x 20A, 2x 32A load circuit breaker.
Battery: 2x 63A battery circuit breaker. |
|
Breaker Fail Detection:
|
Electronic fail detection on both load and battery breakers. |
|
DC Terminals:
|
Load: Tunnel terminals, 16mm² (rear connected)
Battery: Tunnel terminals, 35mm² (rear connected) |
| Low Voltage Disconnect: |
125A battery LVD fitted as standard. |
|
|
|
Mechanical
|
|
|
Dimensions, W, H, D:
|
482.6mm (standard 19” module), 89mm (2U, 3½”), 350mm (13¾”) (390mm with cable strain relief) |
|
Weight:
|
9kg (excluding rectifier modules) |
|
|
| Monitoring & Control: |
Various monitoring options are available via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series brochures. |
|
2U
ultra compact system.
48V
nominal output voltage.
6.0kW
maximum output power.
 |