| Specifications |
View Brochure | Modular Rectifiers | Monitoring |
|
|
|
AC Input:
|
Single phase with surge protection and input 32A MCB (refer to rectifier brochure for full details) |
|
Frequency Range:
|
45-66Hz |
|
Power Factor:
|
>0.99 (full load) |
|
Termination:
|
Single phase. Direct MCB termination for L. 10mm² N, E tunnel terminals. |
|
|
|
DC Output Nominal Voltages:
|
-48V |
|
Max Rated System Output Power:
|
4000W @ -48V DC, 83A max. |
| Polarity: |
Positive earth. 1x RM3048 3000W rectifier or 2x RM2048 2000W rectifiers. |
|
DC Distribution:
|
Load: Max 8x 18mm MCB load circuit breakers.
Battery: Max 2x 18mm MCB load circuit breakers. |
|
Breaker Fail Detection:
|
Electronic fuse fail. (Auxiliaries optional) |
|
DC Terminals:
|
Load: Common: 16mm tunnel terminals.
Battery: Common: 35mm tunnel terminals. |
| Low Voltage Disconnect: |
80A battery LVD fitted as standard. |
|
|
|
Weight:
|
Approx. 10.5Kg |
|
Dimensions H, W, D:
|
620mm, 375mm 80mm |
|
|
| Monitoring & Control: |
Various monitoring options via the Enatel SM30 series of control & supervisory modules. Standard features include full temperature compensation, automated and manual battery testing/equalisation and three voltage-free relay alarm outputs. Options include extension remote I/O PCBs that give an extra 6x digital inputs, 6x analogue inputs and 8x voltage-free relay outputs. For further details, refer to the SM30 series of brochures. |